Coolmay CX3G-24MT

Manwal sa Instruksyon sa Coolmay CX3G-24MT PID PLC Controller

Model: CX3G-24MT | Brand: Coolmay

1. Pasiuna

This manual provides detailed instructions for the installation, operation, programming, and maintenance of the Coolmay CX3G-24MT PID PLC Controller. The CX3G-24MT is a versatile programmable logic controller designed for industrial automation applications, featuring voltage support, high-speed pulse control, and motor drive capabilities. It integrates PID auto-tuning, linear arc interpolation, and supports various communication protocols.

atubangan view of the Coolmay CX3G-24MT PLC controller

Hulagway 1: Atubangan view of the Coolmay CX3G-24MT PLC controller.

2. Tapos sa Produktoview

The Coolmay CX3G-24MT is a compact and powerful PLC controller offering 12 digital inputs (DI) and 12 digital outputs (DO). It supports multiple communication interfaces including RS232, RS485, and CAN, making it highly adaptable for various control systems. Key features include:

  • Highly integrated I/O, supporting up to 80 points in the CX3G series.
  • Supports up to 16 optional AD analog quantities.
  • 6-channel single-phase high-speed counting.
  • Standard 8-channel high-speed pulse output.
  • Advanced features like interrupt handling, linear arc interpolation, and PID auto-tuning.
  • 32K program capacity and 32K retentive registers.

Video 1: Product showcase highlighting the physical features and ports of the Coolmay CX3G PLC.

Labeled diagram of the CX3G PLC components and ports

Figure 2: Labeled diagram of the CX3G PLC components and ports. Key components include: 1. Mounting hole, 2. Terminal block for input signal of power supply, 3. Terminal block of digital output, 4. LED of Digital Input, 5. LED of Digital Output, 6. PWR: Power-up State (RUN: The light is On when the PLC is run), 7. RS485/RS232/CAN, 8. RS485, 9. RS485, 10. RUN/STOP PLC operational switch, 11. Analog output, 12. RS232, 13. DIN-Rail Slot (35mm), 14. Terminal block of digital input, 15. PLC USB programming port.

Diagram illustrating high-speed counting and pulse capabilities

Figure 3: Diagram illustrating the high-speed counting and high-speed pulse capabilities of the PLC.

3. Mga detalye

The following tables detail the specifications for the CX3G series, including the CX3G-24MT model.

3.1 Kinatibuk-ang Detalye

FeatureDeskripsyon
Numero sa ModeloCX3G-24MT
Type sa MotorDC Motor, AC Motor
High-concerned nga kemikalWala
SinugdananMainland China

3.2 CX3G Series Model Specifications

Table of specifications for various CX3G models

Figure 4: Detailed specifications for CX3G models including dimensions, I/O, and features.

ModeloCX3G-16MCX3G-24MCX3G-32MCX3G-48MCX3G-34MCX3G-64MCX3G-80M
Dimensyon85*90*36mm130*90*36mm200*90*36mm285*90*36mm
Giputol nga gidak-on77*99mm122*99mm192*99mm277*99mm
Pag-instalarFixed hole installation and DIN-Rail (35mm)
Mga bahinSupport interrupt, linear arc interpolation, PID auto-tuning. 32K program capacity, 32K retentive register
I/O levelInput: Passive NPN, public terminal isolated
Transistor output: NPN
Relay output: Normally open dry contact
Digital nga I/O8DI/8DO12DI/12DO16DI/16DO24DI/24DO18DI/16DO32DI/32DO40DI/40DO
DO typeTransistor(MT) or mixed(2T6R)Relay(MR) or transistor(MT) or mixed(MRT)
(Relay output: max load 5A/ transistor output: max load 500mA)
High speed counting6 channel single-phase 60KHz or AB(Z) phase 2 channel 60KHz, 1 channel 10KHz
High speed pulse8 channels, Y0-Y3 is 100KHz, Y4-Y7 is 10KHz
High-speed counting + high-speed pulse < 480KHz
Analog I/O (optional)Null6AI/4AO2AI8AI/4AO12AI/8AO16AI/8AO4AI/4AO
AI type (optional)Type E/K/S/T/J thermocouple/ PT100/ PT1000/ NTC10K/ NTC50K/ NTC100K/
0~10V/ 0~5V/ 0-20mA/ 4-20mA
-5V~5V/ -10V~10V (except for CX3G-16M)
AO type (optional)0~10V/ 0-~5V/ 0~20mA/ 4~20mA
-5~5V/ -10~10V (2DA for 1 minus temperature)
Default COM port1 Mini type B USB port, 1 Rs232 (Interface terminal is mouse female port with 8 holes), 2 RS485 ports
OpsyonalDefault 2 RS485 ports can be customized as:
1 RS485, 1 RS232,
or 1 RS485, 1 CAN (2.0A/B),
or 1 RS232, 1 CAN (2.0A/B)
CX3G-48M can add Ethernet port.
Default 2 RS485 ports can be customized as 1 RS485, 1 RS232,
CAN (2.0A/B) port is optional
SoftwareCompatible with WORKS 2

3.3 Analog Input Types and Ranges

Table detailing analog input types and their corresponding ranges

Figure 5: Detailed analog input types and their corresponding temperature/voltage/current ranges.

TypeMga paghulagway
PTPT100 (Range: -200~500℃)
PT1000PT1000 (Range: -200~500℃)
EThermocouple type E (Range: 0~600℃)
E_Thermocouple type E, positive and negative temp. test (Range: -110~730℃)
KThermocouple type K, positive temperature test (Range: 0~1100℃)
K_Thermocouple type K, positive and negative temp. test (Range: -230~1370℃)
TThermocouple type T (Range: 0~400℃)
T_Thermocouple type T, positive and negative temp. test (Range: -230~400℃)
SThermocouple type S (Range: 0~1690℃)
S_Thermocouple type S, positive and negative temp. test (Range: -40~1690℃)
JThermocouple type J (Range: 0~800℃)
J_Thermocouple type J, positive and negative tempe. test (Range: -90~950℃)
NTC10KThermistor 10K (Range: -48~110℃)
NTC50KThermistor 50K (Range: -48~210℃)
NTC100KThermistor 100K (Range: -48~210℃)
V0~10V
V50~5V
V + customized voltage0~customized voltage (e.g., customized as 0~24V, the model is written as β€œV24”)
V_-10~10V
V5_-5~5V
A00~20mA
A44~20mA

4. Pag-setup ug Pag-instalar

The CX3G-24MT PLC controller can be installed using fixed holes or mounted on a 35mm DIN-Rail. Ensure proper ventilation and a stable environment for installation.

4.1 Mga Wiring Diagram

Careful wiring is crucial for the correct and safe operation of the PLC. Refer to the diagrams below for connecting the PLC to other devices and for input/output configurations.

Wiring diagram for connecting CX3G PLC and HMI

Figure 6: Wiring diagram for connecting the CX3G PLC and HMI. This diagram illustrates connections for USB-232 serial port cable, PLC download cable, Mini type-B PLC download cable, HMI programming cable, and DC24V power supply.

Detailed input and output wiring diagrams

Figure 7: Detailed wiring diagrams including an input wiring diagram, relay output equivalent circuit diagram, and transistor output equivalent circuit diagram.

4.2 Mga Protokol sa Komunikasyon

The CX3G-24MT supports a variety of communication protocols, enabling integration with different industrial devices.

Diagram showing PLC supporting multiple communication protocols

Figure 8: Diagram showing the PLC supporting multiple communication protocols, including Mitsubishi programming port, Mitsubishi BD board, Modbus RTU/ASCII/TCP, N:N communication, and EIP protocol, and connections to various devices like sensors, relays, thermocouples, soft starters, and frequency converters.

5. Mga Instruksyon sa Pag-opera

Once the PLC is properly installed and wired, ensure the power supply is stable (DC24V). The 'PWR' LED will illuminate when the PLC is powered on. The 'RUN' LED indicates that the PLC program is actively running. Use the RUN/STOP switch (labeled 10 in Figure 2) to control the PLC's operational state.

6. Pagprograma

The Coolmay CX3G-24MT PLC is compatible with WORKS 2 programming software. You can connect your computer to the PLC via the Mini type B USB port (labeled 15 in Figure 2) or the RS232 port (labeled 12 in Figure 2) for programming and debugging. Software and manuals are available on the Coolmay website o pinaagi sa pagkontak sa suporta sa kustomer.

7. Pagmentinar

To ensure the longevity and reliable operation of your Coolmay CX3G-24MT PLC controller, follow these maintenance guidelines:

  • Hupti ang yunit nga limpyo ug walay abog ug mga tinumpag.
  • Regularly check all wiring connections for tightness and signs of wear.
  • Ensure adequate ventilation around the PLC to prevent overheating.
  • Avoid exposing the unit to excessive moisture, extreme temperatures, or corrosive environments.
  • Periodically back up your PLC programs.

8. Pagsulbad sa problema

If you encounter issues with your CX3G-24MT PLC, consider the following common troubleshooting steps:

  • Walay Kuryente/Mga LED nga Patay: Susiha ang koneksyon sa suplay sa kuryente sa DC24V ug siguroha nga kini naghatag sa husto nga voltage. Verify the power switch is in the 'ON' position.
  • PLC Not Running: Ensure the RUN/STOP switch is in the 'RUN' position. Check your program for errors using the WORKS 2 software.
  • Mga Isyu sa Komunikasyon: Verify the correct cable is used (USB or RS232) and that the drivers are installed on your computer. Check communication settings (baud rate, parity, data bits, stop bits) in both the PLC and the programming software. For Modbus communication, ensure the protocol settings are correctly configured.
  • I/O Malfunction: Check wiring to input/output devices. Verify the status of input/output LEDs on the PLC. Test external devices independently to rule out external faults.

9. Mga Tip sa Gumagamit

  • Programming Software: The PLC is programmed using WORKS 2 software. Ensure you have the latest version for optimal compatibility and features.
  • Modbus Support: This PLC supports Modbus communication. Refer to the programming manual for detailed instructions on configuring Modbus RTU/ASCII/TCP protocols for integration with other devices.
  • Analog nga mga Input: When using optional analog inputs, ensure the correct sensor type (e.g., PT100, Thermocouple, Voltage, Current) is selected in your program to match your hardware.

10. Garantiya ug Suporta

For technical support, software downloads, or further assistance, please contact Coolmay customer service. Software and manuals are provided free of charge and can be obtained from the official Coolmay website or by reaching out to the seller.

May Kalabutan nga mga Dokumento - CX3G-24MT

Si Preview Giya sa Gumagamit sa Coolmay Cloud Platform: Pagrehistro, Pagbugkos, ug Pag-configure
Usa ka komprehensibo nga giya sa paggamit sa Coolmay Cloud nga plataporma alang sa hilit nga operasyon sa PLC, nga naglangkob sa pagrehistro sa account, pagbugkos sa device, pag-configure sa variable sa ulipon, ug pag-setup sa parameter sa network. Gidetalye niini nga dokumento ang mga lakang sa pag-integrate sa Coolmay PLCs sa cloud para sa dugang nga pagmonitor ug pagkontrol.
Si Preview Coolmay PLC Programming Manual V20.81 - Mga Instruksyon ug Operasyon
Komprehensibo nga manwal sa programming para sa Coolmay PLC series controllers (V20.81), nagdetalye sa mga instruksyon, mga operasyon sa device, ug mga prinsipyo sa programming. Nahiuyon sa software sa Mitsubishi.
Si Preview Manwal sa Programming sa Coolmay QM3G Series HMI/PLC All-in-One: Mga Feature, Espisipikasyon, ug Giya sa Operasyon
Kini nga komprehensibo nga manwal sa programming nagdetalye sa Coolmay QM3G Series HMI/PLC All-in-one devices. Naglangkob kini sa mga detalye sa hardware, mga pag-amping sa programming, mga gimbuhaton sa PLC ug HMI, mga protocol sa komunikasyon (Modbus, RS485, CAN, Ethernet), ug paggamit sa software, nga naghatag ug hinungdanong impormasyon para sa mga inhenyero ug mga teknisyan nga nagtrabaho sa mga solusyon sa industrial automation sa Coolmay.
Si Preview Coolmay L02 Series PLC Programming Manual: Features, Specifications, ug Applications
Susihon ang Coolmay L02 Series PLC Programming Manual. Gidetalye niini nga giya ang mga advanced nga bahin sa L02 PLC, arkitektura sa sistema, pagkaangay sa module, mga protocol sa komunikasyon (Modbus, Ethernet/IP), ug mga instruksiyon sa programming. Maayo alang sa industriyal nga automation ug pagkontrol sa mga aplikasyon.
Si Preview Coolmay CM-GPRS User Manual - Wireless Communication Module
Komprehensibo nga manwal sa paggamit alang sa Coolmay CM-GPRS wireless communication module, nagdetalye sa hardware, working modes, data transmission, GPS positioning, ug configuration. Naglakip sa kasayuran sa mga variant sa CM-GPRS-G ug CM-GPRS-L.
Si Preview Coolmay CM500 VFD User Manual
User manual para sa Coolmay CM500 Variable Frequency Drive (VFD), nga naglangkob sa mga pag-amping sa kaluwasan, impormasyon sa produkto, pag-instalar, operasyon, mga parameter, ug pag-troubleshoot.